Mitsubishi Electric MELSEC iQ-R Series User Manual page 78

Profinet io controller module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Item
(11)
Client Identifier
(12)
IP Address
(13)
Sub-Network Mask
(14)
Gateway IP Address
(15)
Permanent
(16)
Blinking Test
(17)
[Device Blinking] button
(18)
Request Status
*1 If the IP address set in GX Configurator-PN of the IO device and the actual IP address of the IO device are different, the RJ71PN92
overwrites the actual IP address with the IP address set in GX Configurator-PN.
*2 Characters from a to z, numbers from 0 to 9, "." (dot), and "-" (hyphen) can be used. "-" cannot be used at the beginning and end of the
name.
The name can be separated by ".". The number of characters in each separated part is limited to 63 or less.
*3 This function may not be used depending on the IO device. For details, refer to the manual of the IO device.
When IO devices on the network are detected on the "Devices on the Network" window, an execution request
is sent from GX Configurator-PN via the RJ71PN92. Connect a personal computer in which GX Configurator-
PN is installed, the RJ71PN92, and target IO device to the same network.
In addition, set the module parameters such as an IP address of GX Works3 and write them to the CPU
module before IO device detection because the execution request is sent from GX Configurator-PN to the IP
address of the RJ71PN92.
3 GX Configurator-PN
76
3.1 Window Structure
Description
Not supported in the RJ71PN92.
Displays the IP address of the selected IO device.
When setting the IP address of the selected IO device, enter a new IP address and click
the [Apply] button.
"Request Status" displays execution results.
Displays the subnet mask of the selected IO device.
When setting the subnet mask of the selected IO device, enter a new subnet mask and
click the [Apply] button.
"Request Status" displays execution results.
Displays the gateway IP address of the selected IO device.
When setting the gateway IP address of the selected IO device, enter a new gateway IP
address and click the [Apply] button.
"Request Status" displays execution results.
Sets to save the TCP/IP setting of the IO device in the non-volatile memory or volatile
memory of the IO device.
• Selected: Saves the setting in the non-volatile memory of the IO device. When the IO
device is restarted, the IP address, subnet mask, and gateway IP address set in (12) to
*3
(14) are used.
• Not selected: Saves the setting in the volatile memory of the IO device. When the IO
device is restarted, the IP address, subnet mask, and gateway IP address are returned
to the default.
Not supported in the RJ71PN92.
Opens the "Blinking Device" window and sends the Blink command to the selected IO
device. The LED of the IO device that has received the Blink command flashes.
Displays execution results of the operation performed in the "Devices on the Network"
window.
Setting range
0.0.0.0 to 255.255.255.255
(Default: IP address of the
current IO device)
0.0.0.0 to 255.255.255.255
(Default: Subnet mask of
the current IO device)
0.0.0.0 to 255.255.255.255
(Default: Gateway IP
address of the current IO
device)
• Selected
• Not selected
(Default: Not selected)