5.2

Electrical connection in the cable connection area

Fig. 7
1 Pushbutton for lower/upper range values | 2 + Signal screw terminals for leads with cross-section of 0.5 ... 1.5 mm
3 - Signal screw terminals for leads with a cross-section of 0.5 ... 1.5 mm
5 Cable entry | 6 Line load | 7 Grounding | 8 Handheld terminal | 9 Resistor (min. 250 Ω) |
10 Power supply / power supply unit | 11 Optional ground | 12 Receiver
application
Transmitter operated outside the potentially explosive atmosphere.
Transmitter operated inside the potentially explosive atmosphere.
WARNING! Risk of explosion!
If, when using transmitters with type of protection "intrinsic safety", an ammeter is connected to the output circuit
or a modem is connected in parallel while there is a risk of explosion, the sums of the capacitances and
inductances of all circuits, including the transmitter (see EC-type-examination certificate) must be equal to or less
than the permissible capacitances and inductances of the intrinsically safe signal circuit (see EC-type-examination
certificate for the power supply unit).
Only passive or explosion-proof devices or indicators may be connected.
16 IM/261Gx/Ax-EN Rev. 08 | 261Gx, 261Ax
2
| 4 Grounding / equipotential bonding terminal (optional) |
Permissible voltage range of power supply
11 ... 42 V
11 ... max. 30 V (intrinsically safe)