90
Input power connection
Voltage (U
)
1
Prospective short-circuit
current (IEC 60439-1)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1
Motor connection
Voltage (U
)
2
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum recommended
motor cable length
Efficiency
Cooling
Method
Free space around the unit
Cooling air flow
Degrees of protection
Technical data
200/208/220/230/240 VAC 3-phase ± 10 % for 230 VAC units
380/400/415 VAC 3-phase ± 10 % for 400 VAC units
380/400/415/440/460/480/500 VAC 3-phase ± 10 % for 500 VAC units
525/550/575/600/660/690 VAC 3-phase ± 10 % for 690 VAC units
For units without an enclosure extension, maximum allowed prospective short-circuit
current in the supply is 65 kA in a second providing that the supply cable of the drive is
protected with appropriate fuses. US: 65,000 AIC.
48 to 63 Hz, maximum rate of change 17 %/s
Max. ± 3 % of nominal phase to phase input voltage
0.98 (at nominal load)
0 to U
, 3-phase symmetrical, U
1
DTC mode: 0 to 3.2 · f
FWP
U
Nmains
f
=
· f
FWP
Nmotor
U
Nmotor
f
: frequency at field weakening point; U
FWP
U
: rated motor voltage; f
Nmotor
0.01 Hz
See section
IEC ratings.
1.5 · P
hd
8 to 300 Hz
3 kHz (average). In 690 V units 2 kHz (average).
Type code (EMC equipment)
-
+E202 *, +E210 *
* Motor cable longer than 100 m (328 ft) is allowed but EMC filtering within the specified limits will not
be achieved.
Approximately 98 % at nominal power level
Internal fan, flow direction from front to top
See
Free space around the
See
IEC ratings.
IP 00 (UL type: open chassis)
at the field weakening point
max
. Maximum frequency 300 Hz.
: mains (input power) voltage;
Nmains
: rated motor frequency
Nmotor
Max. motor cable length
DTC control
300 m (984 ft)
100 m (328 ft)
unit.
Scalar control
300 m (984 ft)
100 m (328 ft)