Mains cable fuses

Fuses for short-circuit protection of the mains cable are listed below. The fuses also
protect the adjoining equipment of the drive in case of a short-circuit. Check that the
operating time of the fuse is below 0.5 seconds. The operating time depends on
the supply network impedance and the cross-sectional area, material and length of
the supply cable. See also Electrical installation planning:
short-circuit
Note 1: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 2: Mains cable sizing is based on a correction factor of 0.71 (max. 9 cables laid on a cable ladder
side by side, ambient temperature 30 °C, EN 60204-1 and IEC 364-5-523). For other conditions, size
the cables according to local safety regulations, appropriate input voltage and the load current of the
drive. You can choose a thicker cable but the fuses must be rated according to the table (bigger fuses
must not be used).
Note 3: Fuses from other manufacturers can be used if they meet the ratings.
ACS800-04 size
Cu (mm
Three-phase supply voltage 380 V, 400 V or 415 V
-0140-3
3x185+95
-0170-3
3x240+120
-0210-3
2x(3x95+50)
-0260-3
2x(3x150+95)
-0320-3
2x(3x240+120)
-0400-3
3x(3x150+95)
-0440-3
3x(3x185+95)
-0490-3
3x(3x185+95)
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0170-5
3x185+95
-0210-5
3x240+120
-0260-5
2x(3x95+50)
-0320-5
2x(3x150+95)
-0400-5
2x(3x240+120)
-0440-5
3x(3x150+95)
-0490-5
3x(3x185+95)
-0550-5
3x(3x185+95)
-0610-5
3x(3x185+95)
protection. For UL recognized fuses, see
Cable
2
2
)
Al (mm
)
3x240+95Cu
2x(3x120+50Cu)
2x(3x150+50Cu)
2x(3x240+95Cu)
3x(3x150+50Cu)
3x(3x240+95Cu)
3x(3x240+95Cu)
3x(3x240+95Cu)
3x240+95Cu
2x(3x120+50Cu)
2x(3x150+50Cu)
2x(3x240+95Cu)
3x(3x150+50Cu)
3x(3x240+95Cu)
3x(3x240+95Cu)
3x(3x240+95Cu)
3x(3x240+95Cu)
US
A
V
Manufacturer
250
500
ABB Control
315
500
ABB Control
315
500
ABB Control
400
500
ABB Control
500
500
ABB Control
630
500
ABB Control
800
500
ABB Control
800
500
ABB Control
250
500
ABB Control
315
500
ABB Control
315
500
ABB Control
400
500
ABB Control
500
500
ABB Control
630
500
ABB Control
630
500
ABB Control
800
500
ABB Control
800
500
ABB Control
Thermal overload and
tables.
Fuse
Type
IEC size
OFAF1H250
OFAF2H315
OFAF2H315
OFAF3H400
OFAF3H500
OFAF3H630
OFAF3H800
OFAF3H800
OFAF1H250
OFAF2H315
OFAF2H315
OFAF3H400
OFAF3H500
OFAF3H630
OFAF3H630
OFAF3H800
OFAF3H800
PDM code: 00096931-B
Technical data
87
1
2
2
3
3
3
3
3
1
2
2
3
3
3
3
3
3