2. Performance Specifications

The performance specifications of the A1S68DAV/DAI are tabled below.
For the general specifications, refer to the user's manual for the PLC CPU are using.
Item
Digital input value
Analog output
I/O characteristics
Maximum resolution of
analog value
Overall accuracy (accuracy
to maximum value)
Maximum conversion time
Output short protection
Analog output points
Insulation method
Offset/gain adjustment
Number of I/O points
Connection terminal
Applicable wire size
Applicable solderless
terminal
Internal current
consumption (5VDC)
Weight
*1 : If the frequency of access from the PLC CPU using FROM/TO instructions is high
(e.g.scan time of 5ms or less with access every scan), this can be extended up to
about 6ms.
*2 : The weight in hardware version "F" or earlier is 0.28kg.
How to check the hardware version
The hardware version for the A1S68DAV/DAI can be checked on the label on the front of
the module.
A
1S68DA
RUN
A1S68DAV
-2048 to 2047
-10 to 0 to 10 VDC
(External load resistance:
2KΩ to 1MΩ)
Digital input
Analog output
value
2000
10V
1000
5V
0
0V
-1000
-5V
-2000
-10V
5mA
±1% (±100mV)
*1
Maximum 4ms
/8 channels
Provided
8 channels/module
Photocoupler insulation between output terminals and PLC power.
Not provided
Special, 32
20 point terminal block (M3.5 × 7screws)
2
0.75 to 1.5mm
R1.25-3, 1.25-YS3A, RAV1.25-3, V1.25-YS3A
0.65A
*2
0.22kg
Front of Module
Specification
0 to 4095
4 to 20mADC
(External load resistance:
0 to 600Ω)
Digital input
value
value
4000
2000
0
4μA
±1% (±200μA)
0.85A
Software Version
Hardware Version
A1S68DAI
Analog output
value
20mA
12mA
4mA