1MRK 511 284-UEN A
7.4
650 series
Engineering manual
Configured IED Description (*.cid) for the IEC 61850 structure as needed
for the IED at runtime.
IED Capability Description (*.icd) for the IEC 61850 structure, see
66.
IEC08000416 V1 EN
Figure 66:
3.
The SCL Export Options window opens.
4.
Select Export Private Sections, Export As SCL Template or Include Goose
Sending IEDs and click Export, see
Export Options window according to
is exported.
IEC08000418 V1 EN
Figure 67:
IEC 61850: Export IED file Options
Engineering of vertical and horizontal communication
in IET600
For IEC 61850 engineering a separate system configuration tool is needed to be used
with PCM600. In PCM600 Ver. 2.3 or earlier the recommended tool is CCT600. In
PCM600 Ver. 2.4 or later the recommended tool is IET600, which is also included in
the PCM600 Engineering Pro installation package. In PCM600 Ver. 2.5, a lot of
engineering described below can be done in the PCM directly.
Procedure for signal engineering for the station by using IET600:
1.
Create a project in IET600.
2.
Import the SCD file exported from PCM600.
IEC 61850 communication engineering
IEC 61850: Export IED file type selection
Figure
Figure 67
IEC08000418.vsd
Section 7
IEC08000416.vsd
67. Note that the options in SCL
is only available when an ICD file
Figure
95