E
C
LECTRONIC
ONTROL
Breaker Ready / Not Ready Binary Output Contacts and Ready Light Status
CONDITION
Capacitor Energy sufficient For O-CO
operations
Capacitor Energy sufficient for CO
operations
Capacitor Energy sufficient for O op-
erations
Capacitor Energy insufficient for any
operations
Close Coil continuity not right
Open Coil continuity not right
APPENDIX C
B
OARD
Ready LED: on
Ready contact: closed
Not ready contact: opened
Ready LED: blinking
Ready contact: closed
Not ready contact: opened
Ready LED: blinking
Ready contact: closed
Not ready contact: opened
Ready LED: off Ready contact:
opened Not ready contact:
closed
Ready LED: blinking Ready
contact: closed Not ready con-
tact: opened
Ready LED: off
Ready contact: opened
Not ready contact: closed
Appendix. Table 4 Circuit Breaker Condition Vs. Position
1VAL050601-MB Rev C
CIRCUIT BREAKER POSITION
CLOSE
Ready LED: on
Ready contact: closed
Not ready contact: opened
Ready LED: blinking
Ready contact: closed
Not ready contact: opened
Ready LED: off
Ready contact: opened
Not ready contact: closed
Ready LED: off
Ready contact: opened
Not ready contact: closed
Ready LED: off
Ready contact: opened
Not ready contact: closed
Ready LED: off
Ready contact: opened
Not ready contact: closed
OPEN
41