■Remote head module operation setting at error detection
Set the operation of the remote head module when an error is detected, in "Remote head Module Operation Setting at Error
Detection" of "RAS Setting" in "CPU Parameter". ( Page 79 RAS Setting)
■Remote head module operation setting
Set the operation of the remote head module when an error occurs in each intelligent function module.
[Navigation window]  [Parameter]  [System Parameter]  [I/O Assignment] tab  [I/O Assignment Setting]
Window
Displayed items
Item
Description
Remote head Module
Set whether to stop or continue the operation of the remote head module
Operation Setting at
when the major or moderate error is detected in the configured module.
Error Detection
When "Stop" is set, the operating status of the remote head module is set to
the STOP state and the cyclic transmission is stopped.
When "Continue" is set, the operating status of the remote head module is
maintained.
When the remote head module is in the STOP state, the operation is as
follows.
• The transfer from the link device (RX, RY, RWr, RWw) of the remote head
module to the user device (X, Y, W) is as follows.
The transfer from RY to Y stops. The transfer from RWw to W stops. The
transfer from X to RX continues. The transfer from W to RWr continues.
• The data transfer between the devices in the remote head module stops.
All outputs of the remote head module are turned off.
Setting range
Default
Critical: Stop, Moderate:
Critical: Stop, Moderate:
Continue
Continue
Critical: Stop, Moderate:
Stop
Critical: Continue,
Moderate: Continue
1 FUNCTIONS
1.5 RAS Function
1
31