No.
Name
Description
SD10
Self-diagnostic
Self-diagnostic
error number
error number 1
SD11
Self-diagnostic
error number 2
SD12
Self-diagnostic
error number 3
SD13
Self-diagnostic
error number 4
SD14
Self-diagnostic
error number 5
SD15
Self-diagnostic
error number 6
SD16
Self-diagnostic
error number 7
SD17
Self-diagnostic
error number 8
SD18
Self-diagnostic
error number 9
SD19
Self-diagnostic
error number
10
SD20
Self-diagnostic
error number
11
SD21
Self-diagnostic
error number
12
SD22
Self-diagnostic
error number
13
SD23
Self-diagnostic
error number
14
SD24
Self-diagnostic
error number
15
SD25
Self-diagnostic
error number
16
SD53
AC/DC DOWN
The number of
AC/DC DOWN
detections
SD60
Number of
Number of
module with
module with
blown fuse
blown fuse
SD61
I/O module
I/O module
verify error
verify error
module
module
number
number
SD80
Detailed
Detailed
information 1
information 1
information
information
category
category code
Details
The maximum of 16 types of error codes are stored into 'Self-diagnostic error
number' (SD10) onwards when the diagnostics detects an error. (The same error
code as one already stored in 'Self-diagnostic error number' (SD10) onwards is not
stored). The 17th error code onwards are not stored. Also error codes are not stored
when 16 types of error codes have already been stored into 'Self-diagnostic error
number' (SD10) to 'Self-diagnostic error number' (SD25).
The value of this register increments by one and stored as a BIN code, each time
input voltage drops to 85% (AC power)/65% (DC power) or less of the nominal value
while the remote head module is carrying out an operation. A counting cycle from 0
to 65535 to 0 is repeated.
The lowest number of module in which a fuse blew is stored.
The lowest I/O number of the module which has an error detected by the I/O module
verification is stored.
Detailed information 1 information category code is stored.
b0 to b7: Information category code
• 0: N/A
• 2: Drive/file information
• 4: Parameter information
• 5: System configuration information
• 6: Number of times information
• 7: Time information
• 24: Failure information
• 27: System switching information
b8 to b15: Not used (fixed to 0)
Set by (setting
timing)
S (Error)
S (Error)
S (Error)
S (Error)
S (Error)
Appendix 4 List of Special Register (SD) Areas