C.3
Setting up custody transfer mode
The device has to be operational and not yet set to custody transfer mode.
1. Configure the functions important for custody transfer measurement, such as the output
setup (pulse, frequency), custody transfer variable and the measuring mode.
2. Once all the functions relevant to custody transfer have been configured, open the front lid
and remove the display module to access the CT DIP switch group. The flowmeter is set
to custody transfer mode by setting the DIP switch (4) in "ON" position as shown in the
figure below.
Figure C-2
Note
Protected parameters
Parameters protected in CT mode are listed in Parameter protection in custody transfer
mode (Page 316).
3. Remove lid lock screw of display lid.
4. Remove display lid.
5. Carefully pull out local display.
6. Set DIP switch to CT mode.
7. Carefully push display back into housing.
8. Remove O-ring from lid.
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA
CT switch (4) "ON"
Custody Transfer

C.3 Setting up custody transfer mode

313