Table 5-11 Requirements for dust particles in the equipment room
Mechanical active
material
Dust particle
Suspending dust
Precipitable dust
Description
Take the following measures to meet the requirements:
Requirements for Corrosive Gases
The room should be free from dusts and corrosive gases, such as SO
5-12 lists the requirements for the corrosive gas concentration.
Table 5-12 Requirements for corrosive gas concentration
Chemical active
material
SO
H
2
NH
Cl
Take the following measures to meet the requirements:
Issue 03 (2016-01-26)
Dust particle diameter ≥ 5 µm
Suspending dust diameter ≤ 75 µm
75 µm ≤ precipitable dust diameter ≤ 150 µm
Use dustproof materials for ground, wall, and ceiling construction.
Use screens on the door and windows facing outside. The outer windows should be
dust-proof.
Clean the equipment room regularly and clean the air filter monthly.
Wear shoe covers and ESD clothing before entering the equipment room.
Unit
mg/m
2
S
mg/m
mg/m
3
mg/m
2
Avoid constructing the room near a place where the corrosive gas concentration is high,
such as a chemical plant.
Ensure the air intake vent of the room is in the prevailing upwind direction from any
pollution source.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
3
Particle /m
3
mg/m
2
mg/m
· h
Concentration
3
≤0.20
3
≤0.006
3
≤0.05
3
≤0.01
5 Appendix
Concentration
4
≤ 3x 10
(no visible dust accumulated
on a workbench in three
days)
≤0.2
≤1.5
, H
S, and NH
. Table
2
2
3
70