Specify the display range and units of the engineering value
•1
corresponding to the electrical high and low values, within the
limits defined in Table 4.3:
THC/RTD
Type
Type B
Type E
Type J
Type K
Type L
Type N
Type R & S
Type T
Pt100
Power 5/2
Power 3/2
Square Root
Custom Linearizer 1
Custom Linearizer 2
Linear
Table 4.3 Limits of Engineering Ranges
Example – for an electrical input range of 4.0 to 20.0mA,
representing a pressure range of 50 to 250 bar, set the 'Low'
value to 50.0 and the 'High' value to 250.0.
Enter the tag name to be displayed on channel indicators and
•1
used to identify the channel in archive files (8 characters max.).
Note. Tags with a high percentage of capital letters and wide
characters such as 'W' or 'M' may appear truncated in some
Operator Views. In such cases, use lower case letters or fewer
characters.
Enter the tag name to be displayed in the Process view and
•1
used in the archive files (20 characters max.).
4 Configuration
°C
°F
Min.
Max.
Min.
–18
1800
0
–100
900
–140
–100
900
–140
–100
1300
–140
–100
900
–140
–200
1300
–325
–18
1700
0
–250
300
–400
–200
600
–325
–999 to +9999
IM/SM1000 Issue 11
Max.
3270
1650
1650
2350
1650
2350
3090
570
1100