Start-Up
Checking and possible fine adjustment of maximum speed
9
After the optimization runs have been executed, the maximum speed must be checked and its setting
corrected if necessary.
If it is necessary to change the maximum speed setting by more than about 10%, the control response
of the speed control loop must be checked. It may be necessary to repeat the speed controller
optimization run or re-optimize the controller manually.
The optimization runs for field weakening and friction motor and moment of inertial compensation must
be repeated every time the maximum speed setting is altered.
Checking the drive settings
10
The optimization runs do not provide optimum results for every application. The controller settings
must therefore be checked by suitable means (oscilloscope, SIMOVIS Trace etc.). In some cases,
manual re-optimization will be necessary.
Manual (post-)optimization (if necessary)
11
Precontrol and current controller for armature and field
Instructions on how to manually set parameters for the precontrol function can be found in Section 7.2
"Manual optimization".
Speed controller
P200
Actual speed filtering
P225
Speed controller P gain
P226
Speed controller integration time
P227
Speed controller droop
P228
Speed setpoint filtering
Note:
P228 is set to the same value as P226 (speed controller integration time) during the speed controller
optimization run (P051=26) (for the purpose of achieving an optimum control response to abrupt
setpoint changes). When the ramp-function generator is used, it may be better to parameterize a lower
speed setpoint filtering value (P228).
Setting of empirical values or optimization using setpoint control boxes according to generally
applicable optimization guidelines.
EMF controller
P275
EMF controller P gain
P276
EMF controller integration time
Setting of empirical values or optimization using setpoint control boxes according to generally
applicable optimization guidelines.
Setting of supplementary functions
12
E.g. activation of additional monitoring functions
NOTE
Freely assignable function blocks are enabled in parameter U977.
For enabling instructions, please refer to Section 11, Parameter List, description of parameters
U977 and n978.
7-16
SIEMENS AG
SIMOREG DC Master
Operating Instructions
02.00
6RX1700-0AD76