Remaining Connection Status - GE L90 Instruction Manual

Line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

STATUS
actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
RTC SYNC SOURCE
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, Other, and None, where "Other" means any less precise source (SNTP,
IEC 103, IEC 104, or DNP). An actual value displays when the relay includes the IEEE 1588 software option.
The
GRANDMASTER ID
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
ACCURACY
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
PORT 1...3 PTP STATE
Disabled is the port's function setting is Disabled
No Signal if enabled but no signal from an active master has been found and selected
Calibrating if an active master has been selected but lock is not at present established
Synch'd (No Pdelay) if the port is synchronized, but the peer delay mechanism is non-operational
Synchronized if synchronized
is the time difference, measured in nanoseconds, between the fractional seconds portion of the time
PTP - IRIG-B DELTA
being received via PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG-
B time.

6.3.17 Remaining connection status

ACTUAL VALUES  STATUS  COMM STATUS REMAINING CONNECT
 COMM STATUS
 REMAINING CONNECT
6
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
For the graphical front panel, the remaining connections refer to TCP connections only.
— The number of IEC 61850 connections remaining.
MMS TCP
— The maximum number of PMU TCP connections matches the number of aggregators. The maximum number of
PMU TCP
aggregators for the N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with a
PMU. The remaining number of aggregators displays here.
6-10
is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
is the present state of the port's PTP clock. The PTP clock state is:
MMS TCP(max 5)
5
MODBUS TCP (max 4)
4
DNP TCP(max 2)
2
IEC-104 TCP(max 2)
2
PMU TCP
1
SFTP (max 4)
4
Range: 0 to 5
Range: 0 to 4
Range: 0 to 2
Range: 0 to 2
Range: 1 to 4
Range: 0 to 4
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL