CHAPTER 5: SETTINGS
The signal used to initiate the autoreclose scheme is the trip output from protection. This signal can be single pole tripping
for single phase faults and three phase tripping for multi-phase faults. The autoreclose scheme has five operating states.
Table 5-42: Autoreclose states
State
Characteristic
Enabled
Scheme is permitted to operate
Disabled
Scheme is not permitted to operate
Reset
Scheme is permitted to operate and shot count is reset to 0
Reclose in progress
Scheme has been initiated but the reclose cycle is not finished (successful or not)
Lockout
Scheme is not permitted to operate until reset received
Autoreclose programs
The autorecloser provides four programs that can cause from one to four reclose attempts (shots). After the first shot, all
subsequent recloses are always three-pole. If the maximum number of shots selected is "1" (only one reclose attempt) and
the fault is persistent, after the first reclose the scheme goes to lockout upon another Initiate signal.
For the three-pole reclose programs (modes 3 and 4), an
connection with the tripping logic to cause a three-pole trip for single-phase faults.
Table 5-43: Autoreclose programs
Mode
Autoreclose
First shot
mode
Single-
phase fault
1
1 & 3 Pole
1 Pole
2
1 Pole
1 Pole
3
3 Pole-A
3 Pole
4
3 Pole-B
3 Pole
The four autoreclose modes are described as follows:
1 & 3 Pole — In this mode, the autorecloser starts the
single-phase initiated, the
timer if the autoreclose is three-phase time delay initiated. If two or more shots are enabled, the second, third, and
fourth shots are always three-pole and start the
1 Pole — In this mode, the autorecloser starts the
fault is three-phase or a three-pole trip on the breaker occurred during the single-pole initiation, the scheme goes to
lockout without reclosing. If two or more shots are enabled, the second, third, and fourth shots are always three-pole
and start the
AR 3-P DEAD TIME 2(4)
3 Pole-A — In this mode, the autorecloser is initiated only for single phase faults, although the trip is three pole. The
autorecloser uses the
AR 3-P DEAD TIME 1
scheme goes to Lockout without reclosing. If two or more shots are enabled, the second, third, and fourth shots are
always three-phase and start the
3 Pole-B — In this mode, the autorecloser is initiated for any type of fault and starts the
shot. If the initiating signal is
are enabled, the second, third, and fourth shots are always three-phase and start the
Basic reclosing operation
Reclosing operation is determined primarily by the
started by the initiate inputs. A reclose initiate signal sends the scheme into the reclose-in-progress (RIP) state, asserting
the
FlexLogic operand. The scheme is latched into the RIP state and resets only when an
AR RIP
breaker 1) or
(autoreclose breaker 2) operand is generated or the scheme goes to the Lockout state.
AR CLS BKR 2
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
AR FORCE 3-P
Second shot
Multi-phase
Single-
fault
phase fault
3 Pole
3 Pole or
Lockout
Lockout
3 Pole or
Lockout
Lockout
3 Pole or
Lockout
3 Pole
3 Pole or
Lockout
AR 1-P DEAD TIME
timer if the autoreclose is three-pole initiated, and the
AR 3-P DEAD TIME 1
AR 3-P DEAD TIME 2(4)
AR 1-P DEAD TIME
timers.
for the first shot if the fault is single phase. If the fault is multi phase the
timers.
AR 3-P DEAD TIME 2(4)
the scheme starts
AR 3P TD INIT
AR MODE
FlexLogic operand is set. This operand can be used in
Third shot
Multi-phase
Single-
Multi-phase
fault
phase fault
fault
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
Lockout
3 Pole or
Lockout
Lockout
3 Pole or
3 Pole or
3 Pole or
Lockout
Lockout
Lockout
timer for the first shot if the autoreclose is
timers.
for the first shot if the fault is single phase. If the
for the first shot. If two or more shots
AR 3-P DEAD TIME 2
and
settings. The reclosing sequences are
AR BKR SEQUENCE
CONTROL ELEMENTS
Fourth shot
Single-
Multi-phase
phase fault
fault
3 Pole or
3 Pole or
Lockout
Lockout
3 Pole or
3 Pole or
Lockout
Lockout
3 Pole or
Lockout
Lockout
3 Pole or
3 Pole or
Lockout
Lockout
AR 3-P DEAD TIME 2
for the first
AR 3-P DEAD TIME 1
timers.
AR 3-P DEAD TIME 2(4)
(autoreclose
AR CLS BKR 1
5-401
5