CONTROL ELEMENTS

5.8.12 Pilot schemes

5.8.12.1 Menu
SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES
 PILOT SCHEMES
This menu is for selection and configuration of protection signaling schemes. All schemes are available for single-pole
5
tripping applications and can be used with one, two, or four-bit communications channels. Choices of communications
channel include Remote Inputs/Outputs and telecommunications interfaces.
For more information, see the Application of Settings chapter.
5.8.12.2 Direct under-reaching transfer trip (DUTT)
SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES  DUTT SCHEME
 DUTT SCHEME
5-376
 DUTT SCHEME
 PUTT SCHEME
 POTT SCHEME
 POTT1 SCHEME
 HYBRID POTT SCHEME
 BLOCKING SCHEME
 BLOCKING1 SCHEME
 DCUB SCHEME
DUTT SCHEME
FUNCTION: Disabled
DUTT SCHEME BLOCK:
Off
DUTT SEAL-IN
DELAY: 0.010 s
DUTT NO OF COMM
BITS: 1
DUTT RX1:
Off
DUTT RX2:
Off
DUTT RX3:
Off
DUTT RX4:
Off
DUTT SCHEME TARGET:
Self-Reset
DUTT SCHEME EVENT:
Disabled
See below
See page 5-378
See page 5-380
See page 5-383
See page 5-384
See page 5-388
See page 5-392
See page 5-393
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled