CHAPTER 5: SETTINGS
The CT failure function detects problems with system current transformers used to supply current to the relay. This logic
detects the presence of a zero-sequence current at the supervised source of current without a simultaneous zero-
sequence current at another source, zero-sequence voltage, or some protection element condition.
The CT failure logic (see later) is based on the presence of the zero-sequence current in the supervised CT source and the
absence of one of three or all of the three following conditions:
Zero-sequence current at different source current (can be different set of CTs or different CT core of the same CT)
Zero-sequence voltage at the assigned source
Appropriate protection element or remote signal
Settings are described as follows. There are four CT FAIL functions with the breaker and half software option and two
without.
— Enables or disables operation of the CT failure element.
CT FAIL 1 FUNCTION
— Selects a FlexLogic operand to block operation of the element during some condition (for example, an
CT FAIL 1 BLOCK
open pole in process of the single pole tripping-reclosing). Local signals or remote signals representing operation of some
remote current protection elements via communication channels can also be chosen.
— Selects the current source for input 1. The most critical protection element should also be assigned
CT FAIL 1 3I0 INPUT 1
to the same source.
— Selects the 3I_0 pickup value for input 1 (the main supervised CT source).
CT FAIL 1 3I0 INPUT 1 PICKUP
— Selects the current source for input 2. Input 2 should use a different set of CTs or a different CT core
CT FAIL 1 3I0 INPUT 2
of the same CT. If 3I_0 does not exist at source 2, then a CT failure is declared.
— Selects the 3I_0 pickup value for input 2 (different CT input) of the relay.
CT FAIL 1 3I0 INPUT 2 PICKUP
— Selects the voltage source.
CT FAIL 1 3V0 INPUT
— Specifies the pickup value for the 3V_0 source.
CT FAIL 1 3V0 INPUT PICKUP
— Specifies the pickup delay of the CT failure element.
CT FAIL 1 PICKUP DELAY
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CT FAIL 1 PICKUP
DELAY: 1.000 s
CT FAIL 1 TARGET:
Self-reset
CT FAIL 1 EVENTS:
Disabled
Range: 0.000 to 65.535 s in steps of 0.001
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled