PRODUCT SETUP
There are two user security access levels, setting and command, for which you can set a password for each. Use of a
password for each level controls whether users can enter commands or change settings. Another option is to specify
setting and/or command access for individual user accounts.
Setting — Allows the user to make any changes to any of the setting values:
Changing any setting
Test mode operation
Command — Restricts the user from making any settings changes, but allows the user to perform the following
operations:
Operating the breakers via front panel keypad
Changing the state of virtual inputs
Clearing the event records
Clearing the oscillography records
Clearing fault reports
Changing the date and time
Clearing the breaker arcing current
Clearing energy records
Clearing the data logger
Clearing the user-programmable pushbutton states
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the L90, the remote password must be used. If the
connection is to the RS232 port of the front panel, the local password must be used.
5
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command
sessions are initiated by the user through the EnerVista software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands:
ACCESS LOC SETG OFF
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
A command or setting write operation is required to update the state of the remote and local security operands
listed.
When a setting password or command password is set or updated, user access with a graphical front panel is
removed. Simply log in again on the graphical front panel.
When the setting password is set or updated, the graphical front panel Access Level displays as Command. This is
because the graphical front panel is a Modbus client and it does not have automatic access to the password
change.
PASSWORD ACCESS EVENTS
5-10
— Asserted when local setting access is disabled
— Asserted when local setting access is enabled
— Asserted when local command access is disabled
— Asserted when local command access is enabled
— Asserted when remote setting access is disabled
— Asserted when remote setting access is enabled
— Asserted when remote command access is disabled
— Asserted when remote command access is enabled
— This setting allows recording of password access events in the event recorder.
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL