(2) Control data
Device
+0
S1
+1
S1
+2
S1
+3
S1
module type
+4
S1
+5
S1
+6
S1
+7
S1
+8
S1
Length of the
+9
S1
+10
S1
186
Item
b15 b14
S1 +0
1
[1] Error completion type
Specifies whether or not clock data setting is required
Instruction
upon error completion.
execution
0: Clock data setting is not required.
type
1: Clock data setting is required.
[2] Arrival monitoring time setting
Specifies the unit of arrival monitoring time
0: Units of 1 second
1: Units of 100 ms
Stores the status after the completion of the instruction.
Completion
0: Completed normally
status
Other than 0: Completed with an error (error code)
Channel
Specifies which channel the host station uses.
used by the
1 to 8 (channel) (
host station
Target CPU
Sets 0000
or 03FF
H
the target CPU module.)
Specifies the IP address of the CPU module of the other
station.
IP address
*2
+4: IP address (lower 16 bits)
setting
S1
+5: IP address (upper 16 bits)
S1
-
(Fixed value)
(1)
When the instruction is executed
Specifies how many times to resend the data in the
event of failure to complete within the monitoring time
set with
S1
Number of
0 to 15 (times)
resends
(2)
When the instruction is completed
Stores how many times the data was resent (and the
result thereof).
0 to 15 (times)
Specifies the monitoring
time allowed before the
completion of the
processing.
If the processing does not
Arrival
complete within the
monitoring
monitoring time, the system
time
resends data until it
reaches the number of
resends specified with
+7.
S1
Specifies the length of the data to be read.
data to be
1 to 960 (words)
read
(Not used)
Description
to
b9 b8 b7 b6
to
0
[2] [1]
0
Page 184, Section 13.1 (4))
. (Either setting provides access to
H
+8.
If the arrival monitoring time
setting is set to 1s with
+0:
S1
1 to 16383: Monitoring time
(set in units of 1 second)
If the arrival monitoring time
setting is set to 100 ms with
+0:
S1
1 to 65535: Monitoring time
(set in units of 0.1 second)
-
Setting range
b1 b0
1
8001
H
8081
H
8101
H
8181
H
-
0001
to 0008
H
0, 03FF
H
1
to FFFFFFFE
H
0
0 to 15
1 to 16383
1 to 65535
1 to 960
-
*1
Set by
User
System
User
H
User
User
H
User
User
System
User