How To Use The Function; Write Operation - Mitsubishi Electric Q03UDVCPU User Manual

Qnucpu series (communication via built-in ethernet port)
Hide thumbs Also See for Q03UDVCPU:
Table of Contents

Advertisement

11.2

How to Use the Function

11.2.1

Write operation

This operation can be performed by storing the IP address to be changed in SD1292 to SD1297 and turning off and on
SM1292 (IP address storage area write request).
(1) Operating procedure
The following shows the write operation flow.
Store the value to be changed in
SD1292 to SD1297
• IP address
• Subnet mask pattern
• Default router IP address
Turn off than on the IP address storage area
Writing to the IP address storage area (flash ROM).
Execute writing to the IP address storage
area (flash ROM).
Confirm the write completion.
• Write complete (SM1293) is turned on.
• Write error (SM1294) is turned off.
Powered off and then on or reset the
When values in the IP address storage area
Setting the IP address of the built-in Ethernet port
Set values in the IP address storage area
(flash ROM) to the IP address of the built-in
Ethernet port
• IP address
• Subnet mask pattern
• Default router IP address
Storing the used IP address
Store the IP address, subnet mask pattern, and
default router IP address, which are used in the
built-in Ethernet port, in SD1260 to SD1265.
Confirm the IP address
• Confirm in the special register
(a)The IP address, subnet mask pattern,
and default router IP address are stored
in SD1260 to SD1265.
172
write request (SM1292).
CPU module.
(flash ROM) are valid.
(Example) When storing the IP address (192.168.3.40 (C0A80328H)) to
SD1292 and SD1293
1) Convert the IP address to be changed from decimal (192.168.3.40) to
hexadecimal (C0A80328H).
2) Store the IP address converted to hexadecimal in the SD.
0328
SD1292
H
C0A8
SD1293
H
* Store the subnet mask pattern and default router IP address in the same way.
Confirm the write failed.
• Write complete (SM1293) is turned on.
• Write error (SM1294) is turned on.
• Error cause is stored in SD1298.
When values in the IP address storage area
(flash ROM) are not set or are invalid.
Setting the IP address of the built-in Ethernet port
Set values in the built-in Ethernet port on the
PLC parameter to the IP address of the built-in
Ethernet port
• IP address
• Subnet mask pattern
• Default router IP address
Store the lower 2 bytes of the
IP address
Store the upper 2 bytes of the
IP address
Perform writing again.
: CPU operation
: User operation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents