Module Specifications
Module Characteristics
Channels
Module ID
Isolation:
User input to logic (optical) and to
frame ground
Group to group
Channel to channel
LED indicators
Backplane current consumption
External power supply
Thermal derating
Configuration parameters
Diagnostics
Input Characteristics
Input Voltage (Differential)
Input Voltage (Common Mode)
Input Impedance
Accuracy (0V common mode):
Resolution
Common mode rejection
Update rate per module
Compatibility
VersaPro Software
VersaMax PLC CPU Firmware
VersaMax Ethernet NIU Firmware
VersaMax DeviceNet, Profibus, or
Genius NIU Firmware
*
In the presence of severe RF interference, (IEC 1000-4-3, 10V/m), accuracy may be degraded to +/-1%. Input
accuracy may be degraded an additional +/-1% with the introduction of input common mode voltage.
GFK-1504K
Chapter 10 Analog Input Modules
Analog Input Module, 15 Bit Differential Voltage 8 Channels
25 degrees C*
0 to 60 degrees C
8 differential, one group
FFFFB008
250VAC continuous; 1500VAC for 1 minute
Not applicable
None
OK LED indicates backplane power is present
5V output: 200mA maximum
None
None
None
Loss of Internal Power
-10V to +10V
-10V to +10V
100K ohms minimum
+/-0.3% typical of full scale, +/-0.5% maximum of full scale
+/-1% maximum of full scale
0.3125mV = 1 count
70db
7.5ms
Version 2.0 or higher
Version 2.10 or higher
Version 1.10 or higher
Planned for future release
10
IC200ALG261
10-25