Configuring Logical Device Properties; Configuring Logical Node Properties - ABB COM600 Series User Manual

Dnp 3.0 serial master (opc) substation management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

3.4.5.
3.4.6.
26
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual
Name
Process Data Confirmation
Lengths
Application Message Data
retries
Information Address Length
Maximum Message Length

Configuring Logical Device properties

Table 3.4.5-1 Logical Device properties
Property/Parameter
Basic
Station/Remote Switch
OPC Path

Configuring Logical Node properties

Table 3.4.6-1 Configuring Logical Node properties
Property/Parameter
Basic
LLN0
Logical Node Class
GGIO1
Value or Value range / Default
Default: Disable
0 to 5
Default: 5
1 to 2
Default: 2
249 to 2048
Default: 2048
Value or Value range/
Default
Value or Value range/ Default
LLN0
1MRS756567
Description
Defines application level con-
firmation handling.
Maximum number of retries of
an application data fragment.
Length of data object address
used in DNP 3.0 messages.
Maximum length of a data link
fragment.
Description
OPC path of the station remote switch
position to be used with this device.
The format is Node#ProgID For OPC
Server#Channel Name\IED
Name\Logical Device Name\Logical
Node Name\Data Object Name e.g.
GW#ABB.Mod-
bus_Serial_OPC_DA_Server.
Instance[1]#Channel1\IED1\LD1
\GGIO1\loc
Description
Logical node class

Advertisement

Table of Contents
loading

Table of Contents