8.3 GOT Side Settings

8.3.1
Setting communication interface
(Communication settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: CLPA
• Controller Type: SLMP
• I/F: Interface to be used
• Driver: Ethernet(SLMP), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

8.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be set and
confirmed in [I/F Communication Setting].For details,
refer to the following.
1.1.2 I/F communication setting
8 - 4
8. SLMP CONNECTION

8.3 GOT Side Settings

Click!
[Controller Setting] from the
8.3.2
Make the settings according to the usage environment.
3.
4.
Item
GOT Net No.
*1
GOT Station
GOT Ethernet
Setting
GOT
Communication
Port No.
Retry
Startup Time
Timeout Time
Delay Time
Message
Format
Communication
data code
Device read
*2
points
Device write
*2
points
Communication detail settings
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the GOT IP address, subnet
mask, default gateway, peripheral
S/W communication port No.,
transparent port No
Set the GOT port No. for the
connection with the Ethernet
module.
(Default: 5031)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times
out.
(Default: 3times)
Specify the time period from the
GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
PLC.
(Default: 0ms)
Set the message format.
(Default: 4E frame)
Set the communication data code.
(Default: Binary code)
Set the device read points.
(Default: 960 points)
Set the device write points.
(Default: 960 points)
Range
1 to 239
1 to 120
8.3.3GOT
Ethernet Setting
1024 to 5010,
5014 to 49152,
49171 to 65534
(Except for 49153
to 49170)
0 to 5times
3 to 255sec
1 to 90sec
0 to 10000
(×10ms)
QnA compatible
3E frame, 4E
frame
ASCII code, Binary
code
1 to 960 points
1 to 960 points