Confirming The Communication State To Each Station (Station Monitoring Function) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal microcomputers, modbus/fieldbus products, peripherals
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

1.6.3
Confirming the communication state to each station (Station monitoring
function)
The station monitoring function detects the faults (communication timeout) of the stations monitored by the GOT. When
detecting the abnormal state, it allocates the data for the faulty station to the GOT special register (GS).
(1) No. of faulty stations
(a) Ethernet connection (Except for Ethernet multiple connection)
Total No. of the faulty CPU is stored.
Device
GS230
(b) Ethernet multiple connection
Total No. of the faulty connected equipment is stored.
Channel
Ch1
Ch2
Ch3
Ch4
POINT
POINT
POINT
When monitoring GS230 on Numerical Display
When monitoring GS230 on Numerical Display, check [mask processing] with data operation tab as the following.
For the data operation, refer to the following manual.
GT Designer3 (GOT2000) Help
Numerical Display (Data Operation tab)
b15 to b8
(00
fixed)
H
Device
b15 to b8
GS280
(00
H
GS300
(00
H
GS320
(00
H
GS340
(00
H
Set [mask processing] to the upper eight bits (b8
to b15) of GS230 on Numerical Display.
1. PREPARATORY PROCEDURES FOR MONITORING
1.6 Checking for Normal Monitoring
b7 to b0
No. of faulty stations
fixed)
No. of faulty stations
fixed)
No. of faulty stations
fixed)
No. of faulty stations
fixed)
No. of faulty stations
1
b7 to b0
1 - 29

Advertisement

Table of Contents
loading

Table of Contents