3-3-2 Performing the operations of HWHP (CAHV)
Text below explains how to perform HWHP (CAHV) operations that target one group or all groups.
3-3-2-1 Performing the operations that target one group
When you click on a group icon in the operation condition monitoring screen that shows the list of all groups,
the operation screen for that group will appear. The items shown in this screen are the current operation
conditions. Modify the items you want to change and click [OK] to confirm the operation details. Click [Cancel]
to return to the previous screen without making any changes.
Note: If the Web browser is configured to block Java Script, the operation window will appear at the left top of the
floor layout screen. If the floor layout window is scrolled down to click the group icon, scroll up the screen to
the left to perform an operation.
ON/OFF
Click to switch to ON or OFF.
Operation mode
Click to switch the operation mode.
Set temperature
Click to adjust the set
temperature.
Schedule
Available/Not Available
Click to switch the schedule
Available or Not Available.
Cancel button
Click to cancel all operations.
Item
ON/OFF
Operation mode
Set temperature
Fan mode
Prohibit remote
controller operation
Schedule Available/Not
Available
3-3-2-2 Performing the operations that target all groups
Click [Batch Operation] from the operation condition monitoring screen, and the screen to set the batch
operation will appear.
After you have made settings on the screen for batch operation, click [OK] and the operation settings for only
the adjusted items will be sent to all the HWHP (CAHV) groups.
Click [ON] or [OFF] to switch to ON or OFF.
Click [Heating], [Heating ECO], [Hot Water] or [Anti-freeze] to switch the operation mode.
Click
to adjust the set temperature.
Note: The temperature setting range is as follows:
Heating: 25-70ºC/77-158ºF
Heating ECO: Invalid
Hot Water: 25-70ºC/77-158ºF
Anti-freeze: Invalid
Click [Normal] or [Snow] to switch the fan mode.
Select the items you do not want the remote controller to control. Click the word part of [ON/
OFF], [Mode], [Set Temp] and switch to prohibit or enable.
Click the button to select Available or Not Available for the schedule settings.
Description
20
Group name
The name of the group is
displayed here.
Fan mode
Click to switch the fan mode.
Prohibit remote
controller operation
Click to select the items
you do not want the remote
controller to control.
OK button