Field Mountable Videographic Recorder
SM500F
Advanced Math (optional)
Type
8 equations provide ability to perform general arithmetic calculations including F0, mass flow (of ideal gases), relative
humidity and emissions calculations
Size
40-character equation
Functions
+, –, /, log, Ln., Exp, X
multiplexer, absolute, relative humidity
Tags
8- and 20-character tags for each block
Update rate
1 enabled Math block is updated every 100 ms
Logic Equations (optional)
Number
8
Size
11 elements each
Functions
AND, OR, NAND, NOR, XOR, NOT
Tags
20-character tag for each equation
Update rate
300 ms
EMC
Emissions & immunity
Meets requirements of IEC61326 for an Industrial Environment
Electrical
Supply ranges
85 V min. to 265 V max. AC 50/60 Hz or
105 V DC min. to 115 V DC
max.
10 V to 36 V DC (optional)
Power consumption
10 W max.15 VA max.
Power interruption protection
No effect for interrupts of up to 20 ms
IM/SM500F Issue 10.1
n
,
, Sin, Cos, Tan, mean, rolling average, standard deviation, high/median/low select,
7 Specification
43