ABB SM500F User Manual page 43

Field mountable videographic recorder
Hide thumbs Also See for SM500F:
Table of Contents

Advertisement

Field Mountable Videographic Recorder
SM500F
Standard Analog Input Modules
Linear Inputs
Millivolts
Milliamps
Volts
Resistance Ω (low)
Resistance Ω (high)
Digital Input Specification
Sample Interval
Input Isolation
Isolation from Rest of Instrument
Analog Input Types
Thermocouple
Maximum
Range °C
B
–18 to 1800
E
–100 to 900
J
–100 to 900
K
–100 to 1300
L
–100 to 900
N
–200 to 1300
R
–18 to 1700
S
–18 to 1700
T
–250 to 300
* For B, R, S and T thermocouples, accuracy is not guaranteed below the value stated.
RTD
Maximum
Range °C
PT100
–200 to 600
IM/SM500F Issue 10.1
Standard Analog Input
0 to 150 mV
0 to 50 mA
0 to 25 V
0 to 550 Ω
0 to 10 kΩ
Switching threshold 4 V – Min. pulse width of On or Off state 500 ms
100 ms per sample
500 V DC channel-to-channel
Galvanically isolated to 500 V DC
Maximum Range
°F
0 to 3270
–140 to 1650
–140 to 1650
–140 to 2350
–140 to 1650
–325 to 2350
0 to 3000
0 to 3000
–400 to 550
0.1 % or ±0.5 °C (0.9 °F) (above –150 °C [–238 °F]) *
Maximum Range
°F
–325 to 1100
Accuracy (% of reading)
0.1 % or ±2 °C (3.6 °F) (above 200 °C [392 °F]) *
0.1 % or ±0.5 °C (0.9 °F)
0.1 % or ±0.5 °C (0.9 °F)
0.1 % or ±0.5 °C (0.9 °F)
0.1 % or ±1.5 °C (2.7 °F)
0.1 % or ±0.5 °C (0.9 °F)
0.1 % or ±1 °C (1.8 °F) (above 300 °C [540 °F]) *
0.1 % or ±1 °C (1.8 °F) (above 200 °C [392 °F]) *
Accuracy (% of reading)
0.1 % or ±0.5 °C (0.9 °F)
7 Specification
Accuracy
(% of reading)
0.1 % or ±20 µV
0.2 % or ±4 µA
0.2 % or ±1 mV
0.1 % or ±0.1 Ω
0.1 % or ±0.5 Ω
41

Hide quick links:

Advertisement

Table of Contents
loading