10 Error messages

No.
Error message
1
Position Measurement
Failure
2
Valve blocked
3
Positioning Timeout
4
Positioning instable
5
Position out of travel
range
6
Zero-Point displacement
8
Setpoint Failure
Electronics
9
Setpoint out of Range
10
Device not calibrated
11
I/P-Converter defect
12
Stroke counter limit
exceeded
13
Travel counter limit
exceeded
14
Electronic Temperature
Measurement Failure
15
Electronic temperature
out of limits
16
Configuration Data failure
17
Electronics - NV chip
defect
18
Non Volatile Data defect
19
Leakage during operation
20
Leakage chamber 1
21
Leakage chamber 2
22
Leakage in actuator
50 OI/EDP300-EN | PositionMaster EDP300
Possible cause
Troubleshooting
Defective position sensor
Replace position sensor
Friction too high
Valve requires repair
High friction
Service valve
Change disturbance
Select "Adaptive Control"
variables
mode
Mounting kit is bent
Check mounting
conditions
Valve seat is damaged
Service valve
Faulty electronics
Replace electronics
Defective PCS card
Replace PCS card
Autoadjust has not yet
Execute Autoadjust
been executed
Contaminated supply air
Check supply air and
pneumatic output stage
Many valve strokes
Service valve
Many valve strokes or
Service valve
vibrating valve
Faulty electronics
Replace electronics
Temperature is too high
Check mounting
or too low
conditions
Output piping mixed up
Check mounting
conditions
Faulty electronics
Replace electronics
Faulty electronics
Replace electronics
Leakage in actuator,
Start "leakage test"
piping, connections, or
positioner
Leakage in chamber 1 of
Check chamber 1 of the
the actuator or
actuator or pneumatics
pneumatics output line 1
output line 1
Leakage in chamber 2 of
Check chamber 2 of the
the actuator or
actuator or pneumatics
pneumatics output line 2
output line 2
Leakage inside the
Check the actuator
actuator
diaphragms
X
X
X
X
X
X
X
X
X
Alarm group
Sensor
Actuator
X
Actuator
X
Configuration
X
Process
X
Process
Electronics
Operation
Configuration
Actuator
Actuator
Actuator
Electronics
Operation
Actuator
Electronics
Electronics
X
Actuator
X
Actuator
X
Actuator
X
Actuator

Hide quick links: