Process Display - ABB PositionMaster EDP300 Operating Instruction

Electro-pneumatic positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

8.2.1

Process display

Fig. 22: Process display (example)
1 Measuring point identifier |
2 Display showing current process values |
3 Symbol indicating button function |
4 Symbol indicating "Parameterization protected"
5 Diagnostic message | 6 Operating mode symbol
The process display appears on the LCD display when the
device is switched on. It shows information about the device
and current process values.
The way in which the current process values (2) are shown
can be adjusted on the configuration level.
Symbol description
Symbol
Description
Call up information level.
When Autoscroll mode is enabled, a  symbol
appears here and the operator pages are
automatically displayed one after the other.
Call up configuration level.
The device is protected against changes to the
parameter settings.
24 OI/EDP300-EN | PositionMaster EDP300
Descriptions of operating modes
Symbol
Operating mode
Adaptive control active
When the PositionMaster EDP300 positioner is
operated in "Adaptive Mode", the control
parameters are automatically optimized to the
operating conditions in small increments. This is
particularly useful if valves and fittings could not be
operated with reference conditions while the
Autoadjust function was in progress.
The self-optimization process in "Adaptive Mode" is
subject to several factors, meaning that incorrect
adjustments could be made over an extended
period. It is recommended that this operating mode
is only activated over several hours and that the
"Fixed control" operating mode is selected following
this.
Fixed control
In contrast to the "Adaptive control" operating
mode, the control parameters are not automatically
adjusted.
Manual setpoint, adaptive control
The valve is adjusted manually within the stroke
range using the
1. Press and hold the relevant operating button for
the desired direction.
2. Additionally, press
switched to high-speed mode.
or
direction buttons.
if the device is to be
CAUTION – Risk of crushing!
Configured stroke limit positions
and stroke times are not effective in
manual mode. When the actuator
moves, there is a risk of crushing.
You must make sure that no-one is
present within the actuator's
working range.