Got Side Settings - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

4.3.2

GOT Side Settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: FUJI
• Controller Type: FUJI MICREX-SX SPH
• I/F: Interface to be used
• Driver: Ethernet (FUJI), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
■ Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
4 - 24
4. CONNECTION TO FUJI PLC
4.3 Ethernet Connection
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
3.
Item
Set the network No. of the GOT.
GOT Net No.
(Default: 1)
4.
Set the station No. of the GOT.
*1
GOT Station
(Default: 1)
Set the GOT IP address, subnet
GOT Ethernet
mask, default gateway, peripheral S/
Setting
W communication port No.,
transparent port No.
Set the GOT port No. for the
GOT
connection with the Ethernet
Communication
module.
Port No.
(Default: 5030)
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the
GOT startup until GOT starts the
Startup Time
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
Delay Time
load of the network/destination PLC.
(Default: 0ms)
*1
Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
Ethernet setting
Range
1 to 239
1 to 254
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
0 to 5times
3 to 255sec
1 to 90sec
0 to 10000(ms)