Application Macro: Abb Standard (Default) - ABB ACS550-01 User Manual

Drive low voltage ac drives
Hide thumbs Also See for ACS550-01:
Table of Contents

Advertisement

32

Application Macro: ABB Standard (Default)

This macro provides a general purpose, 2-wire I/O configuration, with three (3)
constant speeds. This is the default macro. Parameter values are the default values
defined in the "Complete Parameter List for ACS550" on page 40.
Connection example:
• Analog reference (AI1)
• Start, stop and direction (DI1,2)
• Constant speed selection (DI3,4)
• Ramp pair (1 of 2) selection (DI5)
Start-Up
X1
1
SCR
Signal cable shield (screen)
2
AI1
External frequency reference 1: 0
3
AGND
Analog input circuit common
4
10V
Reference voltage 10 VDC
5
AI2
Not used
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0
8
AO2
Output current: 0
9
AGND
Analog output circuit common
Auxiliary voltage output +24 VDC
10 24V
Common for DI return signals.
11 GND
Digital input common for all
12 DCOM1
Start/Stop: Activate to start
13 DI1
Fwd/Rev: Activate to reverse rotation direction
14 DI2
Constant speed selection
15 DI3
Constant speed selection
16 DI4
Ramp pair selection: Activate to select 2nd acc/dec ramp pair.
17 DI5
Not used
18 DI6
19 RO1C
Relay output 1, programmable
20 RO1A
Default operation:
Ready =>19 connected to 21
21 RO1B
22 RO2C
Relay output 2, programmable
23 RO2A
Default operation:
Running =>22 connected to 24
24 RO2B
25 RO3C
Relay output 3, programmable
26 RO3A
Default operation:
Fault =>25 connected to 26
27 RO3B
Input signals
...
10 V
...
20 mA
...
20 mA
2
2
Note 1. The external reference is
used as a speed reference, if the
vector control mode is selected,
Note 2. Code:
0 = open, 1 = connected
Output signals
• Analog output AO1: Frequency
• Analog output AO2: Current
• Relay output 1: Ready
• Relay output 2: Running
• Relay output 3: Fault
ACS550 User's Manual
DI3 DI4
Output
0
0
Reference through AI1
1
0
CONSTANT SPEED
0
1
CONSTANT SPEED
1
1
CONSTANT SPEED
Jumper Setting
J1
...
AI1: 0
AI2: 0(4)
1 (1202)
2 (1203)
3 (1204)
10 V
...
20 mA