Fault Listing - ABB ACS550-01 User Manual

Drive low voltage ac drives
Hide thumbs Also See for ACS550-01:
Table of Contents

Advertisement

120

Fault Listing

Fault
Code
1
2
3
4
5
6
7
8
9
10
Diagnostics
Fault Name In
Panel
Output current is excessive. Check for and correct:
OVERCURRENT
• Excessive motor load.
• Insufficient acceleration time (parameters 2202
2205
ACCELER TIME
• Faulty motor, motor cables or connections.
Intermediate circuit DC voltage is excessive. Check for and correct:
DC OVERVOLT
• Static or transient overvoltages in the input power supply.
• Insufficient deceleration time (parameters 2203
2206
DECELER TIME
• Undersized brake chopper (if present).
Drive heatsink is overheated. Temperature is at or above 115 °C (239 °F).
DEV OVERTEMP
Check for and correct:
• Fan failure.
• Obstructions in the air flow.
• Dirt or dust coating on the heat sink.
• Excessive ambient temperature.
• Excessive motor load.
Fault current. Check for and correct:
SHORT CIRC
• A short-circuit in the motor cable(s) or motor.
• Supply disturbances.
Inverter overload condition. The drive output current exceeds the ratings
OVERLOAD
given in "Ratings" on page 127 of this manual.
Intermediate circuit DC voltage is not sufficient. Check for and correct:
DC UNDERVOLT
• Missing phase in the input power supply.
• Blown fuse.
• Undervoltage on mains.
1
Analog input 1 loss. Analog input value is less than
AI
LOSS
Check for and correct:
• Source and connection for analog input.
• Parameter settings for
2
Analog input 2 loss. Analog input value is less than
AI
LOSS
Check for and correct:
• Source and connection for analog input.
• Parameter settings for
Motor is too hot, as estimated by the drive.
MOT OVERTEMP
• Check for overloaded motor.
• Adjust the parameters used for the estimate (3005...3009).
Panel communication is lost and either:
PANEL LOSS
• Drive is in local control mode (the control panel displays LOC), or
• Drive is in remote control mode (REM) and is parameterized to accept
start/stop, direction or reference from the control panel.
To correct check:
• Communication lines and connections
• Parameter 3002
• Parameters in Group 10: Command Inputs and Group 11: Reference
Select (if drive operation is REM).
Description and Recommended Corrective Action
2).
2).
1 (1301) and 3001
MINIMUM AI
2 (1304) and 3001
MINIMUM AI
PANEL COMM ERROR
ACS550 User's Manual
1 and
ACCELER TIME
1 and
DECELER TIME
1 (1301).
MINIMUM AI
<
AI
MIN FUNCTION
2 (1304).
MINIMUM AI
<
AI
MIN FUNCTION
.
.
.