The default cable connections to the RMIO board of the DSU are shown below.
Terminal block size:
2
cables 0.3 to 3.3 mm
(22 to 12 AWG)
Tightening torque:
0.2 to 0.4 Nm (2 to 4 lbf in.)
* Three-position operating
1
3
switch
2
4
0
1
START
1)
Non-programmable I/O
2)
External alarm/fault indication via
digital input DI4: See parameter 30.04
DI4 EXT EVENT.
3)
External alarm/fault indication via
digital input DI5: See parameter 30.05
DI5 EXT EVENT.
4)
Acknowledgement from the main
breaker (if in use). If there is no main
breaker but the module-in-built
contactors are in use, the contactors
are monitored by the CMIB board.
24 V DC / 115 V AC / 230 V AC
Hardware description
*
Contactor or breaker on/off
X20
1
VREF-
Reference voltage -10 VDC,
1 kohm < R
2
GND
X21
1
VREF+
Reference voltage 10 VDC,
1 kohm < R
2
GND
3
AI1+
By default, not in use. 0(2) ...10 V,
R
> 200 kohm
4
AI1-
in
5
AI2+
By default, not in use. 0(4) ...20 mA,
R
= 100 ohm
6
AI2-
in
7
AI3+
By default, not in use. 0(4) ...20 mA,
R
= 100 ohm
8
AI3-
in
9
AO1+
By default, not in use. 0(4) ... 20 mA,
R
< 700 ohm
10
AO1-
L
11
AO2+
By default, not in use. 0(4) ...20 mA,
R
< 700 ohm
12
AO2-
L
X22
1
DI1
Overtemperature supervision
2
DI2
On / Off
3
DI3
Start (
4
DI4
By default, not in use.
5
DI5
Fault (0)
1)
6
DI6
Reset
7
+24V
+24 VDC max. 100 mA
8
+24V
9
DGND
Digital ground
10
DGND
Digital ground
11
DI7(DIIL) By default, not in use.
X23
1
+24V
Auxiliary voltage output, non-isolated,
24 VDC 250 mA
2
GND
X25
1
RO11
Relay output 1: Running
2
RO12
3
RO13
X26
1
RO21
2
RO22
3
RO23
X27
1
RO31
Relay output 3: Main contactor/
breaker control
2
RO32
3
RO33
< 10 kohm
L
< 10 kohm
L
1)
1)
1)
rising edge start)
2)
3)
4)
Relay output 2: Fault (-1)