2.

Checking on receipt

Examine the state of the material received and its consistency with the content of the order. Should any damage or errors be
found on unpacking, which must be carried out carefully, make the relative notifi cation within and not over 5 days from the receipt
of the material. The notifi cation must indicate the number of the shipping note.
3.

Storage, lifting and weights

The circuit-breaker, protected by an external wooden crate, is fi xed by means of screws to the transport pallet or to the bottom
of the packing case.
If the circuit-breaker has to remain in the warehouse even for a short time before being put into service, after checking it on receipt,
it must be put back in its container and covered with a waterproof sheet.
CAUTION:
- Use a dry, dust-free room free of aggressive chemical agents as a storage room,
- Storage temperature: -40°C ... +70°C
- Position the circuit-breaker and any fi xed part on a horizontal surface, not in direct contact with the fl oor, but
on a suitable support surface (Fig. 5);
- The maximum number of stackable circuit-breakers is indicated in fi gure 6,
- Keep the circuit-breaker in the open position and with the closing springs unloaded to avoid unnecessary
stresses and the risk of accidents to the person.
Fig. 5
With regard to lifting, follow the instructions: the circuit-breakers must be placed on a sturdy supporting surface and lifted, prefer-
ably, by means of a special fork-lift truck. However, the use of ropes is allowed. In this case, the lifting ropes must be hooked up
as shown in the fi gures (the lifting plates are always supplied with the circuit-breaker).
Fig. 7
Table of the circuit-breaker weights (Kg.)
Selective
Fixed version
circuit-
3 poles
breaker
E1
45
E2
50
E3
66
E4
97
E4/f
E6
140
E6/f
Model
L6555
Withdrawable version
4 poles
3 poles
4 poles
54
70
61
78
80
104
117
147
120
160
210
165
Fig. 6
Current
limiting
82
E2L
93
E3L
125
Notes:
165
• The weights indicated in the table are intended for circuit-breakers
complete with PR121, PR122 or PR123 releases and relative current
170
sensors, excluding the accessories.
240
• The withdrawable version includes the moving part in the same conditions
as above, and the fi xed part with horizontal rear terminals.
250
Apparatus
Doc. no.
Fixed version
Withdrawable version
3 poles
4 poles
3 poles
52
63
72
83
110
Emax
1SDH000460R0002
4 poles
80
95
127
Scale
Page No
6/74