ABB Emax E1 Installation And Service Instructions Manual page 10

Low voltage air circuit-breakers emax series
Table of Contents

Advertisement

Circuit-breaker
Iu [A]
E3S/H/V 12
1250
E3S/H/V 16
1600
E3S/H/V 20
2000
E3N/S/H/V 25
2500
E3N/S/H/V 32
3200
E3L 20
2000
E3L 25
2500
E4H/V 32
3200
E4S/H/V 40
4000
E6V 32
3200
E6H/V 40
4000
E6H/V 50
5000
E6H/V 63
6300
Fig. 16
Positioning the fi rst anchoring baffl e of the busbars according to the short-circuit current
Anchoring to the switchgear
HORIZONTAL
P
E1-E2
HORIZONTAL
250
VERTICAL
250
FRONT
FLAT
Fig. 17
Model
L6555
Vertical terminals
Continuous
current-carrying capacity
[A]
35°C
45°C
55°C
1250
1250
1250
1600
1600
1600
2000
2000
2000
2500
2500
2500
3200
3100
2800
2000
2000
2000
2500
2390
2250
3200
3200
3200
4000
3980
3500
3200
3200
3200
4000
4000
4000
5000
4850
4600
6000
5700
5250
VERTICAL
E3-E4-E6
E1-E6
150
150
250
250
Horizontal and front terminalsi
Busbar
Continuous
cross-section
current-carrying capacity
[mm
2
]
35°C
1x(60x10)
1250
1x(100x10)
1600
2x(100x10)
2000
2x(100x10)
2500
3x(100x10)
3000
2x(100x10)
2000
2x(100x10)
2375
3x(100x10)
3200
4x(100x10)
3600
3x(100x10)
3200
4x(100x10)
4000
6x(100x10)
4850
7x(100x10)
--
Apparatus
Doc. no.
1SDH000460R0002
Busbar
cross-section
[A]
[mm
45°C
55°C
1250
1250
1x(60x10)
1600
1600
1x(100x10)
2000
2000
2x(100x10)
2450
2400
2x(100x10)
2880
2650
3x(100x10)
2000
1970
2x(100x10)
2270
2100
2x(100x10)
3150
3000
3x(100x10)
3510
3150
6x(60x10)
3200
3200
3x(100x10)
4000
4000
4x(100x10)
4510
4250
6x(100x10)
--
--
FRONT
FLAT
Emax
2
]
-
Scale
Page No
10/74

Hide quick links: