ABB Emax E1 Installation And Service Instructions Manual page 18

Low voltage air circuit-breakers emax series
Table of Contents

Advertisement

a) Positioning the moving part in the fi xed part in the DISCONNECTED position
Lift the moving part as shown in the paragraph (3) and insert it in the fi xed part guide, tilting it as shown in fi gure 2.
The manual connection must allow the edge (E) of the circuit-breaker guide to slide under the blocks (D) of the fi xed part. Remove
the lifting devices.
The position reached is stable and allows for any inspections of the circuit-breaker.
Push the moving part as far as the stop in the fi xed part.
Close the compartment door.
b) Passing from the DISCONNECTED to the TEST ISOLATED position.
- Make sure that the indicator (9) is in the DISCONNECTED position.
- For the connection procedure, make sure that the key (12) is in the correct position and/or the padlock (14), if any, has been
removed.
- Make sure that the circuit-breaker is open.
- Push the moving part right into the fi xed part.
- Lower the releasing lever (11).
- Insert the crank handle in the corresponding coupling (10).
- Proceed to turn the crank handle clockwise until the TEST ISOLATED indication appears on the indicator (9). During the initial
turns, the crank handle must oppose no any particular resistance to rotation.
- Should it be necessary to carry out offl ine circuit-breaker operations, the crank handle must be removed.
Fig. 30
c) Passing from the TEST ISOLATED position to the CONNECTED position
- Make sure that the circuit-breaker is open.
- Lower the releasing lever (11).
- Insert the crank handle in the corresponding coupling (10).
- Proceed to turn the crank handle clockwise until the CONNECTED indication appears on the indicator (9).
- Remove the crank handle to enable the circuit-breaker to close.
Fig. 31
d) Passing from the CONNECTED position, to the TEST ISOLATED position, to the DISCONNECTED position
- Repeat the connection procedures changing the direction for turning the crank handle to anti-clockwise. Open the door in the
disconnected position.
Model
L6555
14
12
11
10
Apparatus
Doc. no.
11
10
9
Emax
1SDH000460R0002
9
Scale
Page No
18/74

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents