Safety Instructions

These safety instructions are intended for all work on the PQFS. Neglecting these
instructions can cause physical injury and death. All electrical installation and
maintenance work on the PQFS should be carried out by qualified electricians. Do not
attempt to work on a powered PQFS.
After switching off the supply to the PQFS, always wait at least 25 minutes
before
working on the unit in order to allow the discharge of DC capacitors through the discharge
resistors. Always verify by measurement that the capacitors have discharged. DC
capacitors may be charged to more than 800 Vdc.
Before manipulating current transformers, make sure that the secondary is short-
circuited. Never open the secondary of a loaded current transformer.
You must always wear isolating gloves and eye-protection when working on electrical
installations. Also make sure that all local safety regulations are fulfilled.
DANGER: To ensure safe access, supplies to each individual enclosure must be
isolated before opening.
WARNING: This equipment contains capacitors that are connected between phase
and earth. A leakage current will flow during normal operation. Therefore, a good
earth connection is essential and must be connected before applying power to the
filter.
WARNING: Stored energy in capacitors: this equipment contains capacitors.
Check for residual DC voltage before working inside the equipment.
WARNING: There are AC capacitors & DC capacitors connected inside this filter.
Before performing any maintenance work, please short and ground the three line
terminals. The DC capacitor needs 25 mins to discharge after disconnection.
Please wait for this duration before touching any live parts even after discharging
the AC capacitors to avoid electrical shock.
WARNING: Never discharge DC capacitors through short circuit. Always use a
current limiting resistor of minimum 100W.
WARNING: If the ground is defeated, certain fault conditions in the unit or in the
system to which it is connected can result in full line voltage between chassis and
earth ground. Severe injury or death can result if the chassis and earth ground are
touched simultaneously.
Manual Power Quality Filter PQFS ç Safety instructions 7