Table 29: Filter behavior as a function of the PQF-Manager settings for local start/stop and using
PQF-Manager setup for
digital input
Edge ON/OFF
Remark: Vlow = 0 Vdc, Vhigh = 15-24 Vdc
Refer to
Section 7.7.1.2
according to the function required.
The electrical requirements of the digital inputs are as discussed in
Figure 57
shows a cabling diagram for implementing a start function and a stop
function on the first digital input.
24 Vdc
external
supply
-
+
External start/stop
push button
Remark:
(a)
Left hand terminal block when looking from rear, counting from top to bottom
Figure 57: Cabling diagram for implementing start and stop on digital input 1
Once the cabling has been finished,
· The auxiliary fuse box may be closed
· The filter top cover may be replaced including the connection of the PQF-
Manager to the master unit
· The power to the filter may be restored
Remarks:
· The implementation of local start/stop buttons does not inhibit the usage of the
start/stop function on the PQF-Manager.
· When remote control functionality is implemented (cf.
time as local start/stop buttons, the remote control has priority over the local
start/stop buttons. When the local start/stop command has to be given,
deactivate first the remote control functionality by navigating with the PQF-
Manager to the digital input setup menu and setting the digital input associated
with the remote control to 'Disabled'.
· Note that in a multi-unit filter system in which more than one master system is
present, the digital inputs of all masters have to be set up and cabled in the same
way to obtain full redundancy.
1 digital input
Vlow applied to
Vhigh applied to digital input
digital input
No effect
Filter starts on first rising edge, stops on
second rising edge, etc
for guidelines on how to set up the digital inputs
Manual Power Quality Filter PQFS ç Electrical design and installation 67
PQF-Manager
(a)
7
Digital input 1 (15-24Vdc)
(a)
8
9
10
(a)
11
(a)
12
Section
6.12.1) at the same
Section
4.5.