ABB PQFS Installation, Operation And Maintenance Instructions page 167

Power quality filter
Table of Contents

Advertisement

Network frequency tolerance
Maximum rate of frequency variation
Maximum phase jump of network voltage
Network voltage distortion
Minimum network fault level
Voltage notch limits
Line voltage imbalance
Insulation voltage (Ui)
Auxiliary circuit voltage
Neutral connection systems (if any)
Environment class
Compliance with standards
General construction aspects
EMC immunity
EMC emissions
Filter characteristics
RMS output current per power unit type
– Current ratings
– Neutral current ratings
Modularity
Redundancy
Harmonics that can be filtered
Degree of filtering
Filtering efficiency
Response time
+/- 5 %
20%/s
30°
Maximum 20% phase to phase
1 MVA
No voltage notches allowed.
Maximum 5% of phase to phase voltage
690V
230 Vrms
IT, TT, TNC and TNS. Earth current protection type and sensitivity
must be chosen appropriately.
2
EN-60439-1 (1999)
EN/IEC 61000-6-2, Industrial level
EN/IEC 61000-6-4
(a)
(50Hz or 60Hz network).
Unit type 1: 30 A
Unit type 2: 45 A
Unit type 3: 60 A
Unit type 4: 70 A
Unit type 5: 80 A
Unit type 6: 90 A
Unit type 7: 100 A
3 times the current ratings limited to 270A
Up to 4 power units/filter (power units must have same rating).
One power unit per enclosure.
Power units can be master or slave type
For full redundancy combine master units of same rating.
If any unit in a master-master filter system fails, the other units can
keep running.
For limited redundancy combine master with slave units of the same
rating.
If any slave unit in a master-slave filter system fails, the other units
can keep running.
If the master in a master-slave filter system fails, the complete system
stops running.
15 harmonics individually selectable in the range 2
order if the neutral is connected.
20 harmonics individually selectable in the range 2
order if the neutral is not connected.
Programmable per harmonic in absolute terms
Better than 97% of filter rating typically
40 ms typically (10% - 90% filtering)
Manual Power Quality Filter PQFS ç Technical specifications167
nd
th
– 50
harmonic
nd
th
– 50
harmonic

Advertisement

Table of Contents
loading

Table of Contents