The current generator is physically organized in power units. Each filter enclosure
contains one power unit. A PQFS filter can contain up to 4 power units. Power units can
be combined in a master-slave arrangement, or in a master-master arrangement, the
latter giving full operational redundancy. The current rating of different units in a filter
must be of the same rating. Please refer to
possible unit ratings.
In
Figure 14
bridge (1) that is controlled using PWM-switching technology. Information from the filter
controller is sent to the IGBTs through one flat cable. At the output of the inverter a
voltage waveform is generated which contains the desired spectral components (imposed
by the filter controller) as well as high frequency noise (due to the IGBT switching
technology). Coupling impedance consisting of a reactor (3) and a high frequency
rejection filter (4) ensures that the useful voltage components are converted into a useful
current while the high frequency noise is absorbed. The IGBT-inverter is equipped with
DC capacitors that act as energy storage reservoirs (2).
In active filters containing more than one power unit the control information between
different units passes through a CAN control cable.
If a master-master configuration of filter is chosen, all power units incorporate a PQF-
Manager display. If a master-slave configuration of filter is chosen, only the master
enclosure contains a PQF-Manager display. All units contain a DC capacitors preloading
resistor (5) which charges the DC capacitors of the filter unit once the auxiliary fuse box
of the unit(s) is closed. This approach ensures a smooth filter start-up without excessive
inrush currents.
4.4

The PQF main controller

The PQF main controller controls the complete active filter system. Its tasks include:
Figure 15
18 Hardware description ç Manual Power Quality Filter PQFS
it may be seen that each current generator consists of an IGBT-inverter
· Accepting and executing customer requests to stop and start the equipment;
· Calculating and generating IGBT-inverter control references based on the line
current measurements and the user requirements;
· Interface to the IGBT-inverters;
· Measurement of system voltages and currents for control, protection and
presentation purposes.
depicts the controller interface diagram of the PQFS active filter.
Chapter 12
for more information on the