Information on cabling the digital input contacts is given in
Information on setting up the digital inputs with the PQF-Manager is given in
7.7.1.2.
By default, the digital inputs are disabled.
In a master-master filter arrangement, only the master that has the control over the
complete system will monitor its digital outputs. For full redundant functionality, it is
recommended to cable the digital inputs of all the units in the filter system.
2
Digital Outputs 1 to 6
With each digital output different filter conditions can be associated. The association
between the filter condition and the digital outputs is done with the PQF-Manager.
9
gives an overview of the possible PQF-Manager settings for a digital output and the
effect on the corresponding digital output relay.
Table 9: Filter conditions that can be related to the digital outputs
PQF-Manager setting for digital output
Auxil. ON
PQF runs
Full load
Armed
T limit
In standby
Activ. Main
Activ. Aux
Unit miss.
Pg. alarm 1
Pg. alarm 2
Pg. alarm 3
Warning 1
Warning 2
Warning 3
Remarks:
(a)
: In order to set up this function, navigate to [/Welcome/Settings/Customer set./Digital
Outputs]
(b)
: More information on the standby function is given in
(c)
: Different programmable warnings and alarms can be defined. More information on
this subject is given in
(a)
Output relay closes when...
The auxiliary power is present in the main filter
enclosure and the main controller is
communicating with the PQF-Manager
The active filter is 'on' (IGBTs switching) or in
'standby' (main contactor closed but IGBTs not
switching)
The active filter is running under full load
condition
The filter is ON or is in the startup procedure, or
it is stopped in fault condition but will restart as
soon as the fault has disappeared
The filter temperature limit has been reached
and the filter is derating itself to run at a safe
temperature
The filter is in standby
The main active filter settings are activated
The auxiliary active filter settings are activated
One of the filter units in a multi-unit arrangement
is not available (e.g. due to a permanent error),
or has not yet been commissioned.
The programmable alarm 1 is activated
The programmable alarm 2 is activated
The programmable alarm 3 is activated
The programmable warning 1 is activated
The programmable warning 2 is activated
The programmable warning 3 is activated
Section 7.7.1.2