Flex State Parameters - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

PRODUCT SETUP
From user-programmable
pushbuttons logic
sheet 1, 842021A3
5
User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered
separately, the relay order code must be changed to indicate the correct faceplate option. This can be done in
NOTE
the EnerVista software with the Maintenance > Enable Pushbutton command.

5.3.13 Flex state parameters

SETTINGS  PRODUCT SETUP  FLEX STATE PARAMETERS
 FLEX STATE
 PARAMETERS
This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient
monitoring. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are
packed so that 16 states are readable in a single Modbus register. The state bits can be configured so that all states of
interest are available in a minimum number of Modbus registers.
5-96
Figure 5-37: User-programmable pushbutton logic (Sheet 2 of 2)
LATCHED
LATCHED/SELF-RESET
PUSHBUTTON ON
SETTING
Message Priority
= Disabled
= High Priority
= Normal
Instantaneous reset will be executed if any
front panel button is pressed or any new
target or message becomes active.
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
PUSHBUTTON 2 ON
PUSHBUTTON 3 ON
OR
PUSHBUTTON 16 ON
The enhanced front panel has 16 operands;
the standard front panel has 12
PARAMETER 1:
Off
PARAMETER 256:
Off
SETTING
Flash Message Time
0
AND
OR
Instantaneous
reset *
AND
The message is temporarily removed if
any keypad button is pressed. Ten (10)
seconds of keypad inactivity restores
the message.
AND
SETTING
Flash Message Time
0
AND
T
RST
Instantaneous
reset *
FLEXLOGIC OPERAND
ANY PB ON
Range: FlexLogic operand
Range: FlexLogic operand
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
Top Text
= XXXXXXXXXX
T
RST
On Text
= XXXXXXXXXX
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
Top Text
= XXXXXXXXXX
OR
On Text
= XXXXXXXXXX
PUSHBUTTON 1 LED LOGIC
1. If pushbutton 1 LED control is set to off.
Pushbutton 1
LED
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
2. If pushbutton 1 LED control is not set to off.
SETTING
Pushbutton 1
LED
PUSHBTN 1 LED CTL
= any FlexLogic operand