METERING
The C30 is provided with optional PRP capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section in chapter 2 for details
Total Received Port A
Total Received Port B
is a counter for total messages received with an error (bad port code, frame length too short).
Total Errors
Mismatches Port A
and LAN ID in the frame do not match).
Mismatches Port B
and LAN ID in the frame do not match).
6.3 Metering
6.3.1 FlexElements
ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(8)
FLEXELEMENT 1
6
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-1: FlexElement base units
Base unit
DCmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
6.3.2 RxGOOSE analogs
ACTUAL VALUES METERING RxGOOSE Analogs
RxGOOSE
Analogs
6-10
Mismatches Port A:
Mismatches Port B:
is a counter for total messages received (either from DANPs or from SANs) on Port A.
is a counter for total messages received (either from DANPs or from SANs) on Port B.
is a counter for total messages received with an error on Port A (PRP frame, but port received through
is a counter for total messages received with an error on Port B (PRP frame, but port received through
FLEXELEMENT 1
OpSig: 0.000 pu
Description
BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
f
= 1 Hz
BASE
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
RxGOOSE Analog 1
0.000
RxGOOSE Analog 32
0.000
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
I
for the +IN and –IN inputs
BASE
BASE
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES