CHAPTER 6: ACTUAL VALUES
The C30 is provided with optional IEC 61850 capability. This feature is specified as a software option at
the time of ordering. See the Order Codes section of chapter 2 for details.
The
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
All RxGOOSE Online
Input.
6.2.9 RxGOOSE statistics
ACTUAL VALUES STATUS RxGOOSE STATISTICS RxGOOSE 1(16)
RxGOOSE 1
The C30 is provided with optional IEC 61850 capability. This feature is specified as a software option at
the time of ordering. See the Order Codes section of chapter 2 for details.
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
6.2.10 Digital counters
ACTUAL VALUES STATUS DIGITAL COUNTERS DIGITAL COUNTERS Counter 1(8)
DIGITAL COUNTERS
Counter 1
The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
RxGOOSE 1:
Off
RxGOOSE 16:
Off
RxGOOSE 1
stNum:
0
RxGOOSE 1
sqNum:
0
Counter 1
ACCUM:
0
Counter 1 FROZEN:
0
Counter 1 FROZEN:
YYYY/MM/DD HH:MM:SS
Counter 1 MICROS:
0
value refers to the microsecond portion of the time stamp.
COUNTER 1 MICROS
Range: On, Off
Range: On, Off
STATUS
6
6-5