CHAPTER 6: ACTUAL VALUES
This status is relevant to R-GOOSE reception when configured for SSM or ASM reception modes. It is not relevant for GOOSE
or for R-GOOSE in unicast reception mode.
— The unicast mode of R-GOOSE transmission requires Address Resolution Protocol (ARP) for the resolution of the
ARP
network layer address into the MAC layer address. R-TxGOOSE## ARP status On indicates that ARP responses are being
received and the destination MAC address for R-GOOSE transmissions has been obtained. This status remains Off if
TxGOOSE## is not configured for R-GOOSE. It also remains Off if setting R-TxGOOSE1 DST IP is set to a multicast address. In
the case where setting R-TxGOOSE1 DST IP is configured with a unicast address and this status indicates Off, TxGOOSE##
transmission will be off, and therefore communication network diagnosis needs to be carried out.
This status is only applicable for R-GOOSE transmission with setting R-TxGOOSE1 DST IP set to a unicast IP address. It is not
applicable for GOOSE or for R-GOOSE when setting R-TxGOOSE1 DST IP is multicast.

6.4 Metering

6.4.1 FlexElements

ACTUAL VALUES  METERING  FLEXELEMENTS  FLEXELEMENT 1(8)
 FLEXELEMENT 1
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-1: FlexElement base units
Base unit
DCmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE

6.4.2 RxGOOSE analogs

ACTUAL VALUES  METERING  RxGOOSE Analogs
 RxGOOSE
 Analogs
The C30 is provided with optional GOOSE communications capability. This feature is specified as a software
option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
FLEXELEMENT 1
OpSig:
0.000
Description
BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
RxGOOSE Analog 1
0.000
RxGOOSE Analog 32
0.000
× I
for the +IN and –IN inputs
BASE
METERING
6
6-11