GE C30 Instruction Manual page 285

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
Operand type
State
RxGOOSE Boolean
On
Virtual Input
On
Virtual Output
On
The following table lists the operands available for the relay. The operands can be viewed online by entering the IP address
of the relay in a web browser and accessing the Device Information Menu.
Table 5-18: C30 FlexLogic operands
Operand type
Operand syntax
CONTROL
CONTROL PUSHBTN 1 ON
PUSHBUTTONS
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
CYBERSENTRY
ROLE ADMIN ACT
ROLE SUPERVISOR ACT
ROLE ENGINEER ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
ROLE EXTERNAL ACT
AUTHENTICATION FAIL
UNAUTH FW ATTEMPT
UNAUTH SETTING WRITE
DIRECT DEVICES
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIRECT INPUT/
DIR IO CH1 CRC ALARM
OUTPUT CHANNEL
MONITORING
DIR IO CH2 CRC ALARM
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
ELEMENT:
8BIT SWITCH 1 BIT 0
Eight-bit switch
8BIT SWITCH 1 BIT 1
8BIT SWITCH 1 BIT 2
8BIT SWITCH 1 BIT 3
8BIT SWITCH 1 BIT 4
8BIT SWITCH 1 BIT 5
8BIT SWITCH 1 BIT 6
8BIT SWITCH 1 BIT 7
8BIT SWITCH 2 to 6
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
Example of format
Characteristics
[Input Is '1' (= ON) if...]
RxGOOSE Boolean 1 On
The RxGOOSE Boolean is presently in the ON state
Virt Ip 1 On
The virtual input is presently in the ON state
Virt Op 1 On
The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")
Operand description
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
Administrator role is active and is set to true when that is the case
Supervisor role is active and is set to true when that is the case
Engineer role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
External role is active and is set to true when that is the case
Operand set for Failed Authentication self-test and alarm
Operand set for firmware lock self-test and alarm
Operand set for settings lock self-test and alarm
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level
The rate of returned direct input/output messages on channel 1 exceeded
the user-specified level (ring configurations only)
The rate of returned direct input/output messages on channel 2 exceeded
the user-specified level (ring configurations only)
Bit 0 of eight-bit switch 1 asserted (the least significant bit)
Bit 1 of eight-bit switch 1 asserted
Bit 2 of eight-bit switch 1 asserted
Bit 3 of eight-bit switch 1 asserted
Bit 4 of eight-bit switch 1 asserted
Bit 5 of eight-bit switch 1 asserted
Bit 6 of eight-bit switch 1 asserted
Bit 7 of eight-bit switch 1 asserted (the most significant bit)
Same set of operands as shown for 8 BIT SWITCH 1
FLEXLOGIC
5
5-129