9.2.14 Link special register (SW)

(1) Definition
The link special register (SW) is used to store communication status data and error data of intelligent function
modules, such as CC-Link IE controller network modules and MELSECNET/H network modules.
Because the data link information is stored as numeric data, error locations and causes can be checked by
monitoring the link special register.
(2) Number of link special register points
The points for the link special register in the CPU module are 2048 (SW0 to SW7FF).
However, the number of points can be changed in the Device tab of the PLC parameter dialog box.
(
Section 9.1)
The points for an intelligent function module such as a CC-Link IE controller network module or a MELSECNET/H
network module are 512.
By assigning it as shown in Figure 9.42, data of the link special register (SW) in a CC-Link module can be also
refreshed to the link special register (SW) in the CPU module.
Remark
For details of the link special register, refer to the manual for each intelligent function module that has the link special
register.
9 - 34
Link special register
SW0
For 1st network module
SW1FF
SW200
For 2nd network module
SW3FF
SW400
For 3rd network module
SW5FF
SW600
For 4th network module
SW7FF
SW800
For 1st CC-Link module
SW9FF
Figure 9.42 Points of the link special register
512
points
512
points
512
2560
points
points
512
points
512
points