AUP: auxiliary position contacts The AUP contacts are intended for circuit-breakers in withdrawable version.
79 | © 2014 ABB | 1SDH000999R0002 - L8569
They electrically signal the position of a moving part (inserted/test/withdrawn) in relation to the fixed part in
which they are inserted.
These are "switching" contacts and are available, up to a maximum of six contacts per circuit-breaker, in the
following configurations:
• six standard contacts
• six digital signals
The following table provides information on the electrical characteristics:
Characteristics
24V
DC
125V
250V
Breaking
250V
capacity
AC
400V
Minimum load
AUP: Connections
Further information is available on page 58, or on the site http://www.abb.com/abblibrary/DownloadCenter/,
where the wiring diagram is available 1SDM000091R0001.
A4
XF
A3
XF
A4
Diagram 95
Information on the assembly is available from the web site http://www.abb.com/abblibrary/DownloadCenter/,
in particular with the kit sheet 1SDH000999R0603.
Standard
-
0.5A @ 0ms / 0.3A @ 10ms
0.3A @ 0ms / 0.15A @ 10ms
3A cos φ 0,3
5A cos φ 0,7
5A cos φ 1
3A cos φ 1
2A cos φ 0,7
1A cos φ 0,3
50mA @ 24V
102
104
112
114
122
124
132
2
4
2
4
S75E/1
S75E/2
1
1
2
4
2
S75T/1
S75T/2
1
101
111
121
ABB | SACE Emax 2
Digital signals
0.1 A
-
-
-
-
-
-
-
-
1mA @ 5V
95
134
144
142
154
152
4
1
4
2
4
2
S75I/1
S75I/2
1
1
131
141
151
Electrical accessories | 2 - Electrical signalling accessories

Advertisement

Table of Contents
loading

Table of Contents