Electrical Accessories; Electrical Control Accessories; Yo-Yc-Yo2: Opening And Closing Coil - ABB SACE Emax 2 Installation, Operation And Maintenance Instructions

Low voltage air circuit-breakers
Table of Contents

Advertisement

Electrical accessories

1 - Electrical control accessories

YO-YC-YO2: Opening and
closing coil
D1
C1
C11
C3
C13
D2
C2
C12
YU
YC
YO
YO2
72 | © 2014 ABB | 1SDH000999R0002 - L8569
The opening coils, YO and YO2, and the closing coil, YC, allow the circuit-breaker to be controlled remotely.
The opening of the circuit-breaker is always possible with the circuit-breaker closed, while closing is possible
with the circuit-breaker open and the closing springs loaded.
The opening and closing coils can operate in two different modes:
instantaneous service (the minimum duration of the command impulse must be 100ms).
service with permanent power supply.
IMPORTANT:
• In the case of permanent power supply, if the closing coil trips it is necessary, after
opening, to momentarily de-energize the coil in order to be able to re-use it for the
subsequent closing.
• If instead the opening coil trips, it is necessary, after having de-energized it, to wait at
least 100 ms before operating the closing coil.
NOTE: the second opening coil YO2 is alternative to the under-voltage coil YU.
Available voltages and characteristics
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un)
24 V AC/DC
30 V AC/DC
48 V AC/DC
60 V AC/DC
110...120 V AC/DC
220...240 V AC/DC
240...250 V AC/DC
277 V AC/DC
380...400 V AC
415...440 V AC
480...500 V AC
500...550 V AC
General characteristics YO-YO2
Operating limits
70%...110% Un
Inrush power (Ps)
AC= 300VA DC= 300W
Continuous power (Pc)
AC= 3.5VA DC= 3.5W
Opening time
35ms
Closing time
-
ABB | SACE Emax 2
YC
85%...110% Un
-
50ms
Electrical accessories | 1 - Electrical control accessories