p9799
SI reference checksum SI parameters (Control Unit) / SI set_checksum CU
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
0000 hex
Description:
Sets the checksum for the checked Safety Integrated parameters on the Control Unit (reference checksum).
Dependency:
Refer to: r9798, p9899
p9801
SI enable functions integrated in the drive (Motor Module) / SI enable fct MM
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned16
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Sets the enable signals for the safety functions integrated in the drive and the type of selection on the Motor Module.
Not all of the settings listed below will be permissible, depending on the Control Unit and Motor Module or Power
Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9871.0 = 1).
0004 hex:
Extended functions via Terminal Module 54F (TM54F) have been enabled (permissible for r9871.5 = 1).
0005 hex:
Extended functions via Terminal Module 54F (TM54F) and the basic functions via onboard terminals have been
enabled (permissible for r9871.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9871.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9871.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9871.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9871.4 =
1).
0024 hex:
Extended functions without selection are enabled (permissible for r9871.16 = 1).
0025 hex:
Extended functions without selection and basic functions via onboard terminals are enabled (permissible for r9871.16
= 1).
Bit field:
Bit
00
02
03
05
06
Dependency:
Refer to: p9601, r9871
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
STO (SH) via terminals (MM) enable
Enable motion monitoring functions
integrated in drive (MM)
Enable PROFIsafe (MM)
Enab motion monit functions integr in drive
w/out selection (MM)
Basic functions via TM54F
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
FFFF FFFF hex
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Enable
Enable
Enable
Enable
Enable
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2800
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 0000 bin
0 signal
Inhibit
Inhibit
Inhibit
Inhibit
Inhibit
FP
2810
-
-
-
-
939